C Range Surface Air Curtains

The C Range Surface Air Curtains from Thermoscreens are best suited to applications where there is minimal headspace above the door. Air velocity and heating output are suitable for sheltered sites.

If the door way is exposed to prevailing winds you should consider the Thermoscreens standard over the door air curtain for light commercial use (T Range).

Recommended Height: 3m max recommended height
Widths available:            1m, 1.5m and 2m

PRODUCT FEATURES

  • Available in Electric, Water or Ambient
  • ErP compliant
  • Air curtains come in RAL 9010 (white) as standard
  • Low inertia high efficiency electric heating coils in electric heated unit
  • Powerful heat output
  • BMS ready
  • Integrated thermostat
  • 2 year warranty

SUPPLIED WITH

  • Tangential Fans
  • Electric and Water units are supplied with Ecopower energy saving controller
  • 3 Way valve supplied with water units
  • End caps and wall brackets
  • Optional filters available on surface mounted water and ambient units

TECHNICAL SPECIFICATIONS

Models  Dimensions  Supply  Heat  Loading  Max.  Max. Air  Weight  **dB(A) 
  (mm)  (50Hz)  Output  (A) *per  Velocity  Volume  (kg)  @3m 
  (L x D x H)    (kW)  phase  (m/s)  (m3/h)    High Med Low
Ambient
C1000A NT 1137 x 275 x 198 230V~1P&N 0.7 9.0 1250 15 55 53 50
C1500A NT 1669 x 275 x 198 230V~1P&N 0.9 9.0 1800 21 55 53 49
C2000A NT 2200 x 275 x 198 230V~1P&N 1.1 9.0 2500 31 56 54 50
Electric 
C1000E NT 1137 x 275 x 198 400V~3P&N 4.5/9 *13.7 9.0 1250 16 55 53 50
C1500E NT 1669 x 275 x 198 400V~3P&N 6/12 *18.3 9.0 1800 23 55 53 49
C2000E NT 2200 x 275 x 198 400V~3P&N 9/18 *27.2 9.0 2500 33 56 54 50
LPHW 82/71 
C1000W NT 1137 x 275 x 198 230V~1P&N 6 0.7 8.5 1180 18 55 53 50
C1500W NT 1669 x 275 x 198 230V~1P&N 9 0.9 8.5 1700 26 55 53 49
C2000W NT 2200 x 275 x 198 230V~1P&N 12 1.9 8.5 2360 37 56 54 50

**Sound pressure levels (dBA) at 3m, as given above, are for a single air curtain mounted at its maximum mounting height, operating in a room with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s) and a room size equivalent to 8 air changes per hour (ac/h). Care needs to be taken when selecting air curtains for an installation as noise levels can be several dB higher if the mounting height is reduced, if the room is more “live” (i.e. hard surfaces, no furnishings or absorbent materials), if the room is smaller than 8 ac/h equivalent or a combination of these factors. Noise levels will also increase if more than one air curtain is installed at the same doorway (e.g. + 3dBA for 2 equal point sources: direct field).

Models

C1000E NT-9kW 3P
C Range surface mounted Electric 9kW 3Ph 1m
C1500E NT-12KW3P
C Range surface mounted Electric 12kW 3Ph 1.5m
C2000E NT-18KW3P
C Range surface mounted Electric 18kW 3Ph 2m

Look at who is using Thermoscreens Air Curtains

vodafonealditesco_ireland